GWZ-TS4.1 / GWZ-TS6.1
The freely programmable, self-regulating limit monitors are used for indicating the concentration of gases and vapors.
When exceeding or falling below a certain threshold an alarm is triggered.
Similarly, via potential-free relay output, it is possible to activate devices, such as magnetic valves, fans and acoustic transmitters.
The unit is available for DIN rail mounting (TS 35) with 24 V DC power supply.
Up to 6 sensors out of the product range can be connected to the 4 - 20 mA interface. The sensors are supplied via this device with 24 V DC. There is also a digital input for a digital signal contact (e.g. pressure, water level) and a digital input for the external horn reset. The limit monitor has up to 6 potential-free relay outputs which are configured as follows: Via an alpha-numeric display the concentration values of the connected sensors are shown on a rolling basis. Additional status LEDs display information about the operating status, malfunction, horn and alarms. The device can be either configured directly via button and display or being connected by an RS232 interface to a PC. By using the configuration software the device can be easily configured via PC. The limit monitor is available for DIN rail mounting (TS 35) with 24 V DC power supply. With the configurable internal data logger the data of each sensor connected can be recorded and be read again via the PC interface. The device is self- monitoring the wiring of the sensor. It detects wire break and short circuit while triggering a fault message. The malfunction alarm relay is designed fail-safe, means, in case of failure power supply is cut off (closed-circuit principle) and a power failure can thus be detected. The "Inhibit" feature allows freezing the relay status for more than 20 minutes. This prevents from triggering the alarm during maintenance. The limit monitors meets the following directives and standards: The device itself is maintenance free. We recommend regular maintenance for the connected sensors. For this purpose we offer a test gas suitcase or you send the probes to us. Please contact our service center.
All relays are marked in non-operating state.
Connection with up to six sensors and two digital inputs
Relay outputs with test function for alarm, horn and malfunction
A test function allows the verification of the output relay.Control unit with display and status indicator
Configurable on the device or via PC interface
At the limit monitor the following parameters and settings can be programmed for each sensor individually (via button or PC interface):
The limits, the final measuring range value, the unit of measure (LEL, ppm, vol%, °C, etc.), alarms (made either when exceeding or falling below the limit) and alarm output (optionally being stored, not stored or carried as an impulse).Suitable for DIN rail mounting
Configurable data logger
Self-monitoring with fault detection for cable break, short circuit and power failure
"Inhibit" mode of operation
Certifications
Maintenance and Service
Product Name Product Features Product Code
GWZ-TS6.1
6 Measuring channels 4-20 mA
6 Relay outputs
24 V DCD2S0-B04E4
GWZ-TS4.1
4 Measuring channels 4-20 mA
4 Relay outputs
2 Digital inputs 0/24 V DC
24 V DCD2S0-C03E3
General
Power supply
voltage
24 V DC ± 5%
power rating
approx. 3 W (without sensors)
Ambient temperature
-10°C to +50°C
Permissible humidity
15% to 95% relative humidity
non-condensing
Housing
plastic, grey
mounting on DIN rail (TS 35)
protection class
IP 20
weight
approx. 400 g
dimensions (W x H x D)
105 x 71 x 90 mm
Connectors
Port A (measuring system 1)
terminal 18 (out)
24 V DC ± 5%
terminal 19 (in)
4–20 mA; maximum ohmic resistance 370 Ω
terminal 20 (out)
0 V
Port B (measuring system 2)
terminal 21 (out)
24 V DC ± 5%
terminal 22 (in)
4–20 mA; maximum ohmic resistance 370 Ω
terminal 23 (out)
0 V
Port C (measuring system 3)
terminal 24 (out)
24 V DC ± 5%
terminal 25 (in)
4–20 mA; maximum ohmic resistance 370 Ω
terminal 26 (out)
0 V
Port D (measuring system 4)
terminal 27 (out)
24 V DC ± 5%
terminal 28 (in)
4–20 mA; maximum ohmic resistance 370 Ω
terminal 29 (out)
0 V
Port E (measuring system 5)
(GWZ-TS6.1 only)terminal 30 (out)
24 V DC ± 5%
terminal 31 (in)
4–20 mA; maximum ohmic resistance 370 Ω
terminal 32 (out)
0 V
Port F (measuring system 6)
(GWZ-TS6.1 only)terminal 33 (out)
24 V DC ± 5%
terminal 34 (in)
4–20 mA; maximum ohmic resistance 370 Ω
terminal 35 (out)
0 V
Relay malfunction
terminal 6
root
terminal 7
rest contact
non-operating state
failure
Relay alarm 1
terminal 8
root
terminal 9
rest contact
rest contact
alarm 1
Relay alarm 2
terminal 10
root
terminal 11
rest contact
rest contact
alarm 2
Relay alarm 3
(GWZ-TS6.1 only)terminal 12
root
terminal 13
rest contact
rest contact
alarm 3
Relay alarm 4
(GWZ-TS6.1 only)terminal 14
root
terminal 15
rest contact
rest contact
alarm 4
Relay horn
terminal 16
root
terminal 17
operating contact
non-operating state
horn off
External power supply
terminal 1
24 V DC ± 5%
terminal 2
0 V
Relay
potential free changeovers
load 250 V AC, 1 A
powered off system
all relay at rest
Digital interface X1
RS 232
for configuration
Display and Operation
Optical display
yellow LED Error
error message
green LED Power
operation
red LED Horn
audible alarm
red LEDs
A, B, C, D, E, Falarm over channel A, B, C, D, E, F
(channel E, F in GWZ-TS6.1 only)Controls
button F1 and F2
function keys
reset button
horn reset, alarm reset
Alpha-numeric display
measuring plane
concentration, status, fault, threshold exceeded
parameter display
display of measurement ranges, limits, alarm groups
special functions
functional test of the relays, Inhibit mode of operation
Pin assignment
Channel E, F and Alaram 3, 4 in GWZ-TS6.1 only.
Product Name Product Features Product Code
Configurations-Set
Set consisting of:
- CD with configuration software
- connector cable for PC (data cable)Z0A0-D0003
Signal horn-set
24 V DCSet consisting of:
- signal horn, orange, 24V
- warning light, red
- filament lamp 24VZ0A0-E0002
USB-serial adapter
Adapter for connection of RS232 devices plug into the USB port of a PC
Z0A0-H0001