MF420-IR-AL
The measuring system MF420-IR AL determines by using a specific two-beam infrared photometer (NDIR) , developed and produced by our company, the absolute CO2 concentration in the ambient air (atmospheric partial pressure). The device is constantly self-monitoring. The system reports malfunctions of hardware and software and is low-maintenance under normal applications thanks to the NDIR technology - we recommend at least an annual inspection.
The two independent relay outputs can be activated, for example to start automatic window openers, air conditioning or fans.
The MF420-IR AL measures the CO2 concentration between 0-3000 ppm or 0 to 5000 ppm. The standard threshold values in the variant 0-3000 ppm are configured in accordance with the recommendation of the German Federal Environmental Agency. The threshold values can be factory customized individually, within their measuring range, according to customer requirements. The product has two independent relay contacts with max. 10 W (max. 50V switching voltage / max. 0.5 A switching current). The relay contact 2 sends a short pulse when the CO2 concentration exceeds 1,500 ppm, relay contact 1 sends a short pulse when the CO2 level drops below 1,400 ppm. The device complies with the generic standards EN 61000-6-2 and EN 61000-6-4 and thus the EMC Directive 2004/108/EC. The device thanks to its NDIR-Technology is low-maintenance - we recommend at least an annual inspection. For more details, please refer to the technical data or ask our contact person.
For more details, please ask our contact person.
Measuring Ranges and threshould values
< 1500 ppm
LED green
1500 ppm to < 2500 ppm
LED yellow
2500 ppm to < 3000 ppm
LED red
> 3000 ppm
LED red flashing
When exceeding the first threshold value (1500 ppm) a short audible signal will sound and the LED light turns from green to yellow. If the second threshold value (2500 ppm) is exceeded, the LED light turns from yellow to red and the device again triggers an audible alarm. If the third threshold value (3000 ppm) is exceeded, the red LED flashes continuously. If the CO2 concentration falls below the first threshold, the device goes back to the ground state and the green LED lights up again.Relay Connections
Certifications
Maintenance and Service
Product Name Product Features Product Code
MF420-IR-AL
Carbon Dioxide
Measuring range 0 - 3000 ppmG2G0-I09NP-B100
MF420-IR-AL
Carbon Dioxide
Measuring range 0 - 5000 ppmG2G0-I09OP-B100
Principle of Measurement
NDIR (two-beam infrared photometer)
Power Supply
Screw Terminals
Voltage
24 V DC ± 5%
Current
approx. 100 mA
Ambient Temperature
-10°C to +50°C
Air Pressure
900 hPa to 1100 hPa
Permissible Humidity
15 to 95% relative humidity
non condensing
Optical Display
green LED
[CO2] < 1,500 ppm
yellow LED
1,500 ppm < [CO2] < 2,500 ppm
red LED
[CO2] > 2,500 ppm
red LED flashing
[CO2] > 3,000 ppm
Malfunction
Hard- und Software
yellow LED flashing
Output
Terminal 1, relais contact
Typ. Impulse 3.5 s
max. 100 V 0.5 A Switch current
max. 10 VA / W
Impulse at [CO2] < 1,400 ppm
Terminal 2, relais contact
Typ. Impulse 3.5 s
max. 100 V 0.5 A Switch current
max. 10 VA / W
Impulse at [CO2] > 1,500 ppmHousing
Plastic white
Protection class
IP 30
Weight
approx. 150 g
Dimensions (L x W x H)
78 x 78 x 35 mm
Connecting cable
5 x 0.252 Cu
shielded cable
Pin Assignment: